Types of Backflow Assemblies
Choosing the Right Protection
Backflow assemblies are not interchangeable. The assembly must suit the hazard, pressure conditions, approved application and installation requirements. The following overview explains the common types; an existing or proposed installation still needs to be evaluated for its application.
Reduced Pressure Principle Assembly — RP
An RP contains two check valves with a differential-pressure relief valve between them. RPBA, RPZ and RPA are commonly used names for this type of assembly.
Applications can include domestic supplies, irrigation and equipment connections where this type of protection is required. The relief valve can discharge water, so installation planning must account for that discharge and suitable drainage.
An appropriate approved model must be selected for the application. Fire-system installation or replacement is outside Foxfield’s service scope and is referred to a fire contractor.
Double Check Valve Assembly — DC
A DC uses two testable check valves in series and does not have the RP’s differential-pressure relief valve. It is intended for non-health-hazard applications where permitted. DCA and DCBA are other common abbreviations.
A testable double check assembly should not be confused with a dual check device. Permission to use a DC depends on the application and water supplier; its presence elsewhere does not establish that it is acceptable for a new installation.
Pressure Vacuum Breaker — PVB
A PVB is commonly associated with irrigation. It provides protection against backsiphonage and has application and elevation restrictions. It is not a solution for a system subject to backpressure.
Installation height, orientation, access and local acceptance must be checked for the actual assembly and system. A replacement may require a different form of protection when the existing arrangement does not meet applicable requirements.
Spill-Resistant Pressure Vacuum Breaker — SVB
An SVB is a spill-resistant vacuum-breaker assembly used in permitted applications where its operating characteristics are appropriate. Like a PVB, it is intended for backsiphonage conditions rather than backpressure.
Its application, elevation and installation requirements still matter. Identify the model and approved configuration before selecting a replacement; similar appearance alone is not enough.
Detector Assemblies
Detector assemblies combine a primary backflow assembly with a metered low-flow bypass. They are commonly associated with fire services, where the meter helps identify low-flow usage from unauthorized taps or leaks.
RPDA and DCDA identify reduced-pressure and double-check detector arrangements. Type I and Type II configurations differ, so the exact assembly and bypass must be identified for testing, repair and parts selection.
Water-supplier acceptance must be confirmed for the particular configuration. We test and repair these assemblies; fire-service installation and replacement is referred to the appropriate fire contractor.